The Acromag 250T-FQ, 350T-FQ, 450T-FQ are a Frequency Input Loop, DC or AC Power Transmitter.
Firstly, the performance specifications consist of:
Input Ranges: Frequency: span ranges 0 to 25.6KHz, field-selectable, direct coupled inputs, ±25mV to 150V RMS
Output Ranges:
DC Current: 4 to 20mA
DC Voltage: 0 to 5V or 0 to 10V
Power Requirements:
250T: 12 to 50V DC @ 20mA (loop-powered)
350T: DC Voltage Source
Output Range Power
4 to 20mA 10 to 36V DC @ 30mA
0 to 5V 10 to 36V DC @ 9mA
0 to 10V 12.5 to 36V DC @ 9mA
450T: 115V or 230V AC, ±10%, 50 to 60Hz
Output Range Power
4 to 20mA 115V AC @ 0.050A
4 to 20mA 230V AC @ 0.025A
0 to 5V, 0 to 10V 115V AC @ 0.020A
0 to 5V, 0 to 10V 230V AC @ 0.010A
Ambient Temperature Range:
Operating: -13 to 185°F (-25 to 85°C)
Storage: -40 to 185°F (-40 to 85°C)
Accuracy: ±0.1% of calibrated span. Includes repeat ability, hysteresis, terminal point linearity, and adjustment resolution.
Features of the Frequency Input Power Transmitter 250T-FQ, 350T-FQ, 450T-FQ includes:
- Excellent accuracy and stability ensure reliable measurements in harsh industrial environments
- RFI and EMI resistance minimize the effects of environmental noise 90% span adjustment enables precise application calibration
- Quartz crystal time-base design improves temperature performance
- Field-selectable time constants optimize output response time and ripple characteristics
- Selectable threshold circuits accept uni-polar/bipolar inputs (0V bipolar, 1.5V unipolar)
- Excitation/pull-up circuit adds flexibility
- 1500V AC peak isolation (250V AC or 354V DC continuous) prevents ground loops
- 250T models: Input isolated from output/power
- 350T models: Input isolated from output and power. Output and power share a common
- 450T models: 3-way isolation. Input, output, and power circuits are isolated from each other
- Operating temperature range: -25 to 85°C
Contact us for more information.
Reviews