2U Rugged Half-Rack UPS AWB1252-AC

Keep critical electronics running when the primary power supply drops out. The Acumentrics AWB1252-AC rugged half-rack UPS delivers 1,250 VA / 1,000 W of continuous AC output in a compact 2U, 9.4-inch-wide chassis. It accepts AC or DC input and uses a hot-swappable lithium iron phosphate (LFP) battery for backup when both external sources are unavailable.

The AWB1252-AC is designed for compact equipment racks and transit cases housing communications, networking and computing equipment. Metromatics provides sales, technical advice and support across Australia and New Zealand.

Discuss Your Half-Rack UPS Requirements

1,000 W of AC backup power in a 2U half-rack chassis

The Acumentrics AWB1252-AC is a rugged uninterruptible power supply for applications that need AC backup power in a narrow equipment rack or transit case. Its chassis is approximately 239 mm wide and 381 mm deep, making it suitable for space-constrained installations such as mobile communications racks and deployable computing systems.

It accepts 80–265 V AC at 47–440 Hz or 20–32 V DC. When both sources are connected, the UPS prioritises AC input. If AC power drops out, it switches to the external DC source when available, then uses its internal battery if neither external source is available. Acumentrics specifies zero transfer time between sources.

Key features

  • 1,250 VA / 1,000 W continuous output. Supports AC-powered equipment within the unit’s rating. Allow for the published output derating if your AC input can fall into the 80–90 V range.
  • Hot-swappable LFP battery. Acumentrics lists a typical runtime of 13 minutes at 400 W or 5 minutes at 1,000 W, with recharge to 90% in 1.5 hours.
  • AC and DC input with automatic priority. Integrate the UPS with an AC supply and an external DC source where both are available.
  • Optional N+1 paralleling. Configure compatible units for redundancy so the remaining units can carry the critical load if one UPS is unavailable. Confirm the supported configuration when requesting a quote.
  • Local and network monitoring. The unit provides a DB-9 interface and SNMPv3 over Ethernet for remote monitoring.
  • External battery option. Ask Metromatics about the external battery configuration if your required backup time exceeds the published internal battery runtime.

Technical specifications

Acumentrics AWB1252-AC technical specifications
SpecificationAWB1252-AC
Form factor2U rugged half-rack UPS
Continuous AC output power1,250 VA / 1,000 W. Acumentrics specifies linear derating to 1,000 VA / 800 W in the 80–90 V AC input range.
AC input80–265 V AC, single phase, 47–440 Hz
DC input20–32 V DC
AC output115 V AC ±5%, sine wave. Datasheet lists 50 or 60 Hz. Confirm the required frequency when ordering.
Power source priorityAC input, then external DC input, then internal battery
Internal batteryHot-swappable lithium iron phosphate (LFP) battery pack
Typical battery runtime13 minutes at 400 W or 5 minutes at 1,000 W
Battery recharge1.5 hours to 90% charge
Rackmount dimensionsApprox. 89 × 239 × 381 mm (H × W × D)
Overall envelopeApprox. 89 × 239 × 432 mm (H × W × D)
Weight with internal batteryApprox. 9.1 kg (20 lb)
Operating temperature−20°C to +50°C with battery. −40°C to +50°C without battery.
CommunicationsDB-9 interface and SNMPv3 via RJ45 Ethernet

 

Environmental and platform requirements

Acumentrics states that the AWB1252-AC is designed to meet requirements under MIL-STD-461 for electromagnetic compatibility and MIL-STD-810 for environmental conditions. The datasheet also lists requirements for vehicle power, airborne electronics and shipboard installations. If your project specifies a standard, send us the revision and test methods so we can confirm the supporting documentation for your configuration.

Download the Acumentrics AWB1252-AC datasheet (PDF)

Request a quote for the AWB1252-AC

Send us your available AC and DC supplies, required AC output voltage and frequency, connected load, minimum backup time and rack dimensions. Metromatics can help confirm whether the internal battery meets your runtime requirement and whether an external battery or redundant configuration suits your installation.

Discuss Your Half-Rack UPS Requirements

 

AWB1252-AC Rugged Half Rack UPS